2-6 Installation & Wiring
Controller Input Wiring (cont’d)
Figure 7—Controller Input Wiring (See Figures 5 & 6 for Terminal Block Locations)
-
-
Sourcing Devices
(+VDC is being switched)
Sinking Devices
(DC common is being switched)
Term. Function
1-8 Program Select
9 Group 1 Input
10 Group 2 Input
11 Group 3 Input
12 Group 4 Input
13 Group 5 Input
14 Group 6 Input
15 First Cycle Enable
16 Output Enable
Input Wiring Guidelines
• Voltage from TB 2 will be the same as the voltage supplied to the controller.
• Each input powered from TB 2 will draw 11 mA at 24 VDC. TB 2 is fused at 1/4 amp.
• Inputs will operate with voltages from 10 to 30 VDC.
• An external power supply can be used instead of TB 2 to power inputs.
• A combination of mechanical and solid state devices can be used.
• TB 1 can be wired for sourcing while TB 3 is wired for sinking, and vice versa.
-
-